Cáp mạng Dintek CAT.6 UTP (1101-04023, 100 mét/thùng)
Part Number: 1101-04023
- Cáp mạng CAT.6 UTP Dintek 4-pairs, 23AWG, 100m/thùng.
- Khoảng cách truyền tín hiệu: 100 mét.
Features
- Conductor sizes for Cat.6 are set at 23AWG
- By keeping the gauge size of the conductor larger, there is less heat generation caused and less drop of voltage over distance
- Capable of handling the latest version of power over ethernet
- Cable has been tested over 500Mhz and has shown performance testing results allowing 10Gbit Ethernet transmission up to a length of 70mtrs
Standards Conformance
- ACMA approved to AS/CA S008
- ISO/IEC11801 2nd edition CLASS E
- ANSI/TIA-568-2.D standard
- CENELEC EN 50173-1, CENELEC
- PoE++ & 4PPoE - IEEE 802.3bt level 3 & 4
- Flame Rated: CM
Independent Verified Certifications
- Verified to ANSI/TIA-568-2.D Cat.6 102661868CRT-001b
- ACMA approved to AS/CA S008
Specifications
Construction | |
Conductor | |
Material | Bare Copper |
Wire Size | 23AWG |
Insulation | |
Material | PE |
Thickness | Nominal: 1.011 mm |
Colors | Blue/White-Blue | Orange/White-Orange | Green/White-Green | Brown/White-Brown |
Unaged Elongation(%) | Min. 300% |
Unaged Tensile Strength | Min. 1.683 Kgf/mm² |
Jacket | |
Material | Flame Retardant PVC |
Thickness | 0.5 ± 0.02 mm |
Diameter | 6.0 ± 0.2 mm |
Color | Gray (assorted upon request) |
Fire Rated Class | CM |
Physical Ranges | |
Insulation | |
Min. Tension Strength | Before Aging: Min. 1.683 Kgf/mm² | After Aging: 75% before aging (100℃ X 48hrs) |
Min Elongation (%) | Before Aging: 300% | After Aging: 75% before aging (100℃ X 48hrs) |
Jacket | |
Min. Tension Strength | Before Aging: Min. 1.407 Kgf/mm² | After Aging: 75% before aging (100℃ X 168hrs) |
Min Elongation (%) | Before Aging: Min. 100% | After Aging: 50% before aging (100℃ X 168hrs) |
Dielectric Strength | 2500 VDC / 2 seconds |
Min. Bending Radius | 50 mm |
Max. Pulling Tension | 25 lbs |
Installation Temperature | 0℃ to +50℃ |
Operating Temperature | -20℃ to +70℃ |
Electrical | |
Conductor Resistance | Max. 7.32 Ω/100m at 20℃ |
DC Resistance Unbalance | Max. 2% |
Pair-to-Ground Capacitance Unbalance | Max. 160 pF/100m |
Dielectric Strength of Insulation | 2500 V dc / 2 seconds |
Insulation Resistance Test | Min. 5000 MΩ·Km |
Mutual Capacitance | Max. 5600 pF/100m |
Impedance 1~100MHz | 100Ω ± 15% |
Impedance 100-250MHz | 100Ω ± 22% |